Engineering · Electrical — Load Sharing

After two AC generators are paralleled, the division of real (kW) load between them is adjusted by:

Explanation

Real power (kW) follows the prime mover input, so kW load is shifted by trimming the engine governors. Reactive (kVAR) load is shared by adjusting the voltage regulators/excitation. The two are controlled independently.

Authority: Modern Marine Engineer's Manual; AC load sharing