When activating a fixed CO2 total flooding system, what must be done BEFORE releasing the CO2?

Explanation

The correct sequence for a CO2 total flooding system is: sound the pre-discharge alarm, evacuate all personnel from the space, close all vents and openings to maximize agent concentration, then release the CO2. Leaving ventilation open dilutes the CO2 below its minimum design concentration and the fire will not be suppressed. Any personnel remaining in the space will be asphyxiated.